Radon Testing at Radford Army Ammunition Plant
Abstract:
Radon testing of buildings in all geological areas of Radford Army Ammunition Plant showed only 11 buildings of the 511 tested had radon levels greater than 4.0 picocuries per liter of air 4.0 pCi1. Alpha track monitors were used for 3-month screen tests of these buildings. Any buildings having a radon content greater than 4.0 pCi1 were tested for 12-months. Mitigation by air dilution reduced the radon content in 10 buildings to less than 4.0 pCi1. Ducts are being installed in the 11th building to also reduce the radon content by air dilution.
Security Markings
DOCUMENT & CONTEXTUAL SUMMARY
Distribution:
Approved For Public Release
Distribution Statement:
Approved For Public Release; Distribution Is Unlimited.
RECORD
Collection: TR