Abstract:

EMP isolation provided by RFI filters in the SAFEGUARD North Dakota site is evaluated. A mathematical model of typical filters is developed. Comparisons with manufacturing acceptance specifications and with test measurements onsite are used to confirm the model. Isolation of EMP transietnts in th SAFEGUARD installation is shown to be at least 50 dB.