Large Scale Fire Tests of Building Riser Cables,

Descriptive Note:

Corporate Author:

BELL TELEPHONE LABS INC NORCROSS GA

Report Date:

1982-11-01

Pagination or Media Count:

6.0

Abstract:

The National Electrical Code requires that riser cables have sufficient fire resistance so they will not spread fire from floor to floor in a shaft. Fire tests were conducted as the initial task in developing a test method for determining compliance with the Code. The tests provided data on the flame propagation characteristics of riser cables in a simulated riser shaft, the design of which was based on information from a field survey. The data indicated that with a large ignition source, simulating burning combustibles in a shaft without fire stops, some cables propagated fire from floor to floor others, utilizing newer fire resistive materials, did not exhibit the same propensity to promulgate fire. Author