DID YOU KNOW? DTIC has over 3.5 million final reports on DoD funded research, development, test, and evaluation activities available to our registered users. Click
HERE to register or log in.
Accession Number:
ADA399480
Title:
Prototype Early Warning Fire Detection System: Test Series 4 Results
Descriptive Note:
Interim rept. Jan-Jun 2001
Corporate Author:
NAVAL RESEARCH LAB WASHINGTON DC
Report Date:
2002-02-15
Pagination or Media Count:
63.0
Abstract:
This test series has demonstrated the successful operation of the early warning fire detector EWFD system over twelve compartments on two decks of the ex-USS Shadwell providing continuous monitoring of the spaces. The EWFD system responded to both flaming and smoldering fires while maintaining an immunity to nuisance sources. The use of multiple sensors and the Probabilistic Neural Networks alarm algorithm in the EWFD system resulted in improved performance compared to only an ionization or photoelectric smoke detector. The improved performance was illustrated in the comparative results of the EWFD system and the system sensor smoke detectors that were used as part of the EWFD system.
Distribution Statement:
APPROVED FOR PUBLIC RELEASE