Accession Number:

ADA371872

Title:

Aircraft Hangar Fire Suppression System Evaluation-Intermediate- Scale Studies

Descriptive Note:

Interim rept. 1997

Corporate Author:

NAVY TECHNOLOGY CENTER FOR SAFETY AND SURVIVABILITY WASHINGTON DC

Report Date:

1999-12-23

Pagination or Media Count:

44.0

Abstract:

Tests were conducted at the Chesapeake Beach Detachment CBD of the Naval Research Laboratory NRL to evaluate the effect of water sprays on AFFF foam blankets. The tests show that application rates of AFFF above 4.1 Lpmm2 resulted in little improvement in extinguishing times. For the AFFF application rate cited above, the extinguishment times were decreased by an overhead water sprinkler application rate of 6.5 Lpmm2 0.16 gpmft2. The burnback times were affected by the overhead water sprinklers. The burnback time for JP-8 was less than for JP-5 with the overhead sprinkler activated.

Subject Categories:

  • Safety Engineering