Accession Number:

ADA285275

Title:

Corrosion Control Acceptance Criteria for Sacrificial Anode Type, Cathodic Protection Systems

Descriptive Note:

User Guide

Corporate Author:

CONSTRUCTION ENGINEERING RESEARCH LAB (ARMY) CHAMPAIGN IL

Report Date:

1994-07-01

Pagination or Media Count:

28.0

Abstract:

The Army currently operates and maintains more than 20,000 underground storage tanks and over 3000 miles of underground gass pipelines, all of which require some form of corrosion control. Cathodic protection is one method of corrosion control used to prevent corrosion-induced leaks when a steel structure is exposed to an aggressive soil. The corrosion control acceptance criteria for sacrificial anode type CP systems provides guidelines for the DEH DPW cathodic protection installation inspectors whose responsibilities are to ensure that the materials and equipment specified are delivered to the job site and subsequently installed in accordance with the engineering drawings and specifications. The sacrificial anode CP acceptance criteria includes all components for the sacrificial anode system such as insulated conductors, anodes, anode backfills, and auxiliary equipment. The sacrificial anode CP acceptance criteria is composed of a checklist that lists each component and that contains a space for the inspector to either check yes or no to indicate whether the component complies with the job specifications. In some cases, the inspector must measure and record physical dimensions or electrical output and compare the measurements to standards shown in attached tables.

Subject Categories:

  • Industrial Chemistry and Chemical Processing
  • Electrical and Electronic Equipment
  • Metallurgy and Metallography
  • Structural Engineering and Building Technology

Distribution Statement:

APPROVED FOR PUBLIC RELEASE