Title:

B-2 Fire Protection System Infloor Nozzle Trafficking Test

Descriptive Note:

Final rept. Aug-Sep 1992

Corporate Author:

APPLIED RESEARCH ASSOCIATES INC ALBUQUERQUE NM

Report Date:

1993-03-01

Pagination or Media Count:

14.0

Abstract:

This program evaluated the potential damage sustained by the B-2 fire protection system in-floor nozzle housing and cap when exposed to trafficking by a load cart placing loads on the housing similar to a fully loaded B-2 or munitions transporter. Two-hundred and fifty passes of a 25,000 pound, 250 psi load cart were applied to the nozzle housing and cap without damage to either. The pull-off force tests resulted in average pull-off forces that were well within the force produced by the activated fire suppression system. Painting the cap-container interface however, is not recommended. Fire suppression system, B- 2 Hangar

Subject Categories:

  • Safety Engineering