Accession Number:

ADA114320

Title:

Development of a Low Cost EMP Protection Concept for Emergency Operations Centers.

Descriptive Note:

Final rept. Oct 70-Sep 81,

Corporate Author:

NAVAL CIVIL ENGINEERING LAB PORT HUENEME CA

Personal Author(s):

Report Date:

1982-01-01

Pagination or Media Count:

64.0

Abstract:

Electromagnetic pulse EMP shielding, isolation, and protection for emergency operations center type communications equipments has been reduced to a minimum size and cost through development testing, utilizing a concept of shielding, single entry, and in-line transient voltage protection. Shielding for direct induced EMP is balanced against protectors for direct connected EMP to result in EMP voltages at equipment input connections on the order of 5 to 10 volts peak with simulated EMP fields on the order of 10 kVm and direct connected EMP of thousands of volts peak. Author

Subject Categories:

  • Civil Defense
  • Nuclear Radiation Shielding, Protection and Safety
  • Non-Radio Communications

Distribution Statement:

APPROVED FOR PUBLIC RELEASE