Abstract:

A series of marine fouling experiments was conducted at Freeport, Texas, on two single-pass titanium heat exchangers. The exchangers, which were constructed with commercially pure titanium tubes 58-inch 1.59-centimeter outside diameter by 30-inch 76.3-centimeter length and 6Al-4V alloy tube sheets and headers, were operated on natural seawater. One of the exchangers was fed electrolytically chlorinated seawater, while the other was run with untreated seawater feed. Velocity and chlorination levels were varied to determine the effect of these two variables on fouling of the titanium surfaces. Operating conditions similar to those that might be expected in shipboard heat exchangercondenser usage were modeled.

Subject Categories:

  • Metallurgy and Metallography
  • Air Conditioning, Heating, Lighting and Ventilating
  • Marine Engineering

Distribution Statement:

APPROVED FOR PUBLIC RELEASE