DID YOU KNOW? DTIC has over 3.5 million final reports on DoD funded research, development, test, and evaluation activities available to our registered users. Click
HERE to register or log in.
Accession Number:
AD0857124
Title:
Initial Production Test of Air Conditioner, 36,000 BTU/HR, 60-HZ, Single-Package
Descriptive Note:
Final rept. 24 Feb-13 Jun 1969
Corporate Author:
ABERDEEN PROVING GROUND MD MATERIEL TESTING DIRECTORATE
Report Date:
1969-07-01
Pagination or Media Count:
57.0
Abstract:
This report summarizes the initial production test of the 36,000 Btu hr, single-package air conditioner. The purpose of the test was to determine conformance of the air conditioner to required performance characteristics. The results show that a fractured refrigerant line weld, a broken filter retaining spot weld, and a broken compressor motor-winding terminal wire resulted from laboratory vibrations. Also, heavy rusting of the stators and armatures of all motor contactors resulted from exposure to humidity. It is concluded that the air conditioner met the test objectives with the exceptions noted.
Distribution Statement:
APPROVED FOR PUBLIC RELEASE