Accession Number:

AD0857124

Title:

Initial Production Test of Air Conditioner, 36,000 BTU/HR, 60-HZ, Single-Package

Descriptive Note:

Final rept. 24 Feb-13 Jun 1969

Corporate Author:

ABERDEEN PROVING GROUND MD MATERIEL TESTING DIRECTORATE

Personal Author(s):

Report Date:

1969-07-01

Pagination or Media Count:

57.0

Abstract:

This report summarizes the initial production test of the 36,000 Btu hr, single-package air conditioner. The purpose of the test was to determine conformance of the air conditioner to required performance characteristics. The results show that a fractured refrigerant line weld, a broken filter retaining spot weld, and a broken compressor motor-winding terminal wire resulted from laboratory vibrations. Also, heavy rusting of the stators and armatures of all motor contactors resulted from exposure to humidity. It is concluded that the air conditioner met the test objectives with the exceptions noted.

Subject Categories:

  • Air Conditioning, Heating, Lighting and Ventilating

Distribution Statement:

APPROVED FOR PUBLIC RELEASE