Accession Number:

AD0625436

Title:

THE STUDY AND EVALUATION OF ABSORPTION-BASED COOLING SYSTEMS FOR USE IN CIVIL DEFENSE SHELTERS

Descriptive Note:

Final rept., 1 Jul 1964-31 Jul 1965

Corporate Author:

STANFORD RESEARCH INST MENLO PARK CA

Personal Author(s):

Report Date:

1965-12-30

Pagination or Media Count:

87.0

Abstract:

A study has been made of various absorption cycle cooling units and associated components which would be required to maintain a habitable atmosphere in certain identified civil defense fall-out shelters, independent of any external energy sources. Of the many criteria which could be applied to these systems, four were selected as the bases for the final evaluation, e.e., cost, electrical requirement, volume and weight. The selected system consists of the aqueous ammonia absorption cycle cooling unit with heat rejection directly to ambient air from finned-tube condenser and absorber. This unit produces chilled water which is circulated through a finned-tube conditioning coil within the shelter area. Shelter heat is transferred to the chilled water by blowing shelter air and ventilation air through the conditioning coil. Heat to operate the absorption unit is supplied by combustion gases from a furnace designed to burn a volatile-producing fuel with coal as the preferred fuel. Manual power is applied to pump the chilled water and to circulate shelter air and cooling air. A suitably designed furnace needs to be developed, and the normally gas-fired absorption unit must be adapted to the furnace.

Subject Categories:

  • Air Conditioning, Heating, Lighting and Ventilating
  • Civil Defense
  • Nuclear Radiation Shielding, Protection and Safety

Distribution Statement:

APPROVED FOR PUBLIC RELEASE