Accession Number:

AD0601253

Title:

POWER DISTRIBUTION FOR HIGH-RELIABILITY QUADRUPLE-DIVERSITY COMMUNICATIONS SYSTEMS.

Descriptive Note:

Corporate Author:

JACKSON AND MORELAND INC BOSTON MA

Personal Author(s):

Report Date:

1963-02-08

Pagination or Media Count:

22.0

Abstract:

The object of this study is to make recommendations for a conceptual power distribution layout suitable for high-reliability quadruple-diversity communication system stations having a six engine-generator, double-bus, primary power plant. As a result of these studies, the distribution systems principal features are 1 Two generators manually transferable between busses. 2 Two non-transferable generators per bus. 3 Technical and Interruptible Electronics loads manually transferable between busses. 4 Half the Utility load connected to each bus and not transferable between busses. 5 interruptible Electronics and Utility loads on either bus shed automatically upon loss of an operating generator on that bus.

Subject Categories:

  • Radio Communications

Distribution Statement:

APPROVED FOR PUBLIC RELEASE