Accession Number : AD1031494


Title :   Demonstration of Energy Savings in Commercial Buildings for Tiered Trim and Respond Method in Resetting Static Pressure for VAV Systems


Descriptive Note : Technical Report,01 Sep 2014,01 Feb 2017


Corporate Author : Iowa State University Ames United States


Personal Author(s) : Zhou,Xiaohui ; Harberl,Nicholas ; Cheng,Hwakong


Full Text : https://apps.dtic.mil/dtic/tr/fulltext/u2/1031494.pdf


Report Date : 01 Mar 2017


Pagination or Media Count : 249


Abstract : For existing buildings with variable air volume (VAV) system and direct digital control at the zone level, a modified version of the Trim and Respond method, the Tiered Trim and Respond (TTR) method, was implemented at five existing Iowa Army National Guard facilities to show energy savings compared to Fixed Pressure Control method. Comparisons were made by alternating static pressure control modes every two weeks between fixed static control and TTR control over a one year period at these facilities. Demonstration results showed that total fan energy savings for the five demonstration sites ranged from 14.4 to 34.8 compared with fixed static pressure control. Reduction in overall GHG emissions at five sites ranged from 0.6 to 4.7 . Simple payback years are 1.7, 4.9, 5, 11.8 and 14.9 years. Users (building occupants and facility engineers) mostly had no additional comfort complaints. The potential reduction in site energy across DoD installations could be 295 GWh per year, and the potential electricity cost savings could be 29.5 million per year.


Descriptors :   static pressure , energy consumption , cost analysis , control systems engineering , BUILDINGS AND STRUCTURES


Subject Categories : Human Factors Engineering & Man Machine System


Distribution Statement : APPROVED FOR PUBLIC RELEASE