Accession Number : AD1029789


Title :   Removal of Direct Current Link Harmonic Ripple in Single Phase Voltage Source Inverter Systems Using Supercapacitors


Descriptive Note : Technical Report


Corporate Author : Naval Postgraduate School Monterey United States


Personal Author(s) : Hernandez,Gabriel D


Full Text : https://apps.dtic.mil/dtic/tr/fulltext/u2/1029789.pdf


Report Date : 01 Sep 2016


Pagination or Media Count : 89


Abstract : For an Energy Management System (EMS)-controlled microgrid that uses a single-phase voltage source inverter (VSI) configuration to supply power for AC loads from DC energy storage devices, the DC link connecting the VSI to the DC energy storage devices experiences a voltage ripple that is a second-order harmonic of the AC frequency. When the EMS has a battery bank as the only DC energy storage device, the DC link voltage ripple causes a second-order harmonic ripple in battery current that leads to a reduction in battery life. Supercapacitors (SCs), which are capable of operating through many more cycles than batteries, can be added to the EMS to form a battery and SC Hybrid Energy Storage System (HESS).The EMS can then be used to filter out the second-order harmonic ripple in battery bank current and provide this current solely from the SC bank, extending battery life and reducing system operating costs. The design of a computer simulation of an EMS providing power to a microgrid is discussed in this thesis. Simulations provide theoretical results and laboratory results compare well with the theoretical results, showing that SCs can be used to remove the second-order harmonic current ripple from the battery bank.


Descriptors :   energy management , voltage source inverters , hybrid power , supercapacitors , power electronics , power converters , battery chargers


Distribution Statement : APPROVED FOR PUBLIC RELEASE